Hydrotrol Water Hammer Arresters
 
PLACEMENT OF HYDROTROLS ON EXTRA LONG BATTERIES
All Sizing and Placement Data is in Accordance with Plumbing and Drainage Institute Standard P.D.I. WH-201
PLACEMENT ON EXTRA LONG BATTERIES LONG RUNS OF PIPING TO SINGLE FIXTURES, APPLIANCES OR EQUIPMENT
It is recommended that for extra long branches (in excess of 40' in length), the water supply should tie into the branch at some mid-point location. The example shows a branch of approximately 60' in length which can be fed at some mid-point location; thus applying Rules #1 and #2 at either side of the feed line for sizing and placement.

PLACEMENT ON EXTRA LONG BATTERIES


SIZING AND PLACEMENT IN MULTI-STORY BUILDINGS

By using Rules #1 and #2 almost every battery situation can be sized and the HYDROTROLS properly located. Fig. 1 shows the method of sizing and placement in a typical multi-story building which has a great variety of fixtures and fixture locations.


SIZING AND PLACEMENT IN MULTI-STORY BUILDINGS
Table 3 indicates the size HYDROTROL required for long runs of piping which feed a single remote fixture or appliance. HYDROTROL unit should be sized by using Table 3 and located as close to the point of quick closure as possible.


Long Runs

Note: Table 3 shows lengths of run of branch piping. The length of run used should be the length of the pipe from the point of valve closure to a point of relief, such as a large pipe twice the size of the branch line, main line or water tank.

All sizing recommendations shown in Table 3 are based on an operating water pressure of 65 PSI or under and an average velocity between 5 and 10 feet per second. If operating pressures are over 65 PSI use the next larger HYDROTROL unit. When pressures are anticipated above 85 PSI a pressure reducing valve is recommended.


Sizing Example
 