INSTALLATIONS - GREASE INTERCEPTORS
SINGLE FIXTURE INSTALLATIONS

Fixed not Trapped
Fixture Not Trapped

Fixed Trapped and Vented Separately
Fixture Trapped and Vented Separately

Fully Recessed
Fully Recessed

Recessed with Extension to Floor Level
Recessed with Extension to Floor Level

MULTIPLE FIXTURE INSTALLATIONS

It is sometimes practical to discharge the waste from two or more sinks into a single Interceptor. This practice is only recommended when all fixtures are close together, avoiding installation of long piping runs to the Interceptor. For multiple installations, size as follows:

  1. Determine total capacity of all sinks.
  2. Establish the maximum simultaneous discharge of the sinks and fixtures.
  3. Using the maximum simultaneous load capacity, determine the Interceptor required using the sizing method shown by clicking here.

 

On Floor Installation

On Floor Installation

 Terminate Air Intake outside above the rim of sink with return bend or connect to vent or vent stack as required by local code.

GREASE INTERCEPTORS WITH EXTENSION INSTALLATION NOTE

The Extension of 8200 Series Interceptors is designed to increase the roughing dimension from the Inlet-Outlet center line to the finished floor. The Extension should not be used to support the entire unit. When installed in ground floor locations, the Interceptor body must rest on solid ground or on a suitable concrete pad. If the 8200 Series unit is installed in an upper floor (suspended in the ceiling below), a suitable method of supporting the entire unit must be provided. The installation sketch shows a typical Interceptor with Extension and a recommended method of supporting the entire weight.

SUSPENDED INTERCEPTOR INSTALLATION CONSIDERATIONS

Whenever an interceptor is to be installed suspended with receiving cradle (8300 series) or independently (all other series interceptors), proper support is essential for safety and functional integrity of the installation.

Trapeze type hangers such as those employed for support of multiple runs of horizontal piping are recommended for support of independent interceptors. Such supports should also be considered for 8300 series receiving cradles to supplement the integral concrete anchor flange. Supports must be of sufficient strength for the purpose intended and meet with the approval of the architect or engineer.

DISHWASHER MACHINES

A separate grease Interceptor is recommended with each dishwashing machine. The size of the Interceptor is determined by the dishwasher capacity.

 Dishwasher Installation

Terminate Air Intake outside above the rim of sink with return bend or connect to vent or vent stack as required by local code.

  Interceptor Section Index   Technical Data Index   Go Back   Go Forward