| REMEDIATOR® GREASE TREATMENT SYSTEM GUIDE SPECIFICATIONS AND APPROVALS | |
|
Remediator® Grease Treatment System
Guide Specifications
|
Suggested Engineers Specifications-
Figure 8970 Project Specifications: Grease Treatment System shall be as manufactured by Jay R. Smith Mfg. Co.®, 2781 Gunter Park Drive East, Montgomery, AL 36109-1405 and as noted in the contract documents. Grease Treatment System Specifications: Furnish and install a Jay R. Smith Mfg. Co.® figure 8970 Series Remediator® fat, oil and grease (FOG) internal disposal and treatment system with a ___ GPM flow rating and grease capacity twice that of the PDI retention requirement of ____ lbs (Refer to Smith’s sizing criteria and select a 20, 35, 50, or 75 GPM unit). The unit shall be constructed from stainless steel with aluminum diamond plate cover and be furnished complete with vertical vortex media, microprocessor controlled metering pump with low supply alarm, external flow control fitting, bridge trap and Culture reservoir. The main intercepting unit shall be manufactured with integral internal and external test ports. The system shall include a stainless steel solids interceptor with a stainless steel mesh lined basket for disposal of solids. The solids interceptor shall also be provided with a stainless steel mesh lining on the outlet. The system shall be tested and certified by the Plumbing and Drainage Institute as being in conformance with Standard PDI-G101. Where jurisdiction applies, the system shall be listed by an accredited listing agency as a FOG DISPOSAL SYSTEM, certified by independent, accredited laboratory testing as releasing less than 100 mg/L FOG. An alternative system must include each of the specified features and documented test results. Options |
|
|
|
|
|